Good grief there a lot of settings in that meter
The C20 rate works because it calculates the SOC using the Peukert exponent, but I noticed the default Peukert exponent is
1.25 and I just ran the calculations for a
Trojan T-875 (C20=170AH , C5=145AH) and the
Peukert exponent is
1.13.
I kind of like the "
Remaining time at the current rate of discharge" display as it really shows what matters the most for a user